We have a Mori Seiki SL 204 CNC Lathe with MAPPS MSG-501 Controller. Spindle and Servo Amplifiers are MDS-C1-SPM & MDS-C1-V2 Series from Mitsubishi.
Occasionally during CNC operation, Spindle would suddenly stop and rock forward /reverse for few seconds. CNC would then generate Servo Alarm "
PR 003E" & the Mitsubishi Spindle drive "MDS-C1-SPM-260" show an alarm '3E' on its 7 segment LED display. To overcome this fault, we would do a total machine shut down and restart all over. Machine would again work good, until such time the above happens again.
From a machineries dealer, we picked up a used, but working Spindle Amplifier module "MDS-C1-SPM-260" (same as above model) and replaced it on our machine, to solve the above nagging issue.
But now when we start the Spindle with this 'new drive', CNC would instantly generate a "Servo Alarm
PR 0032" & the 'new' Spindle drive shows an alarm 32 on its LED display. Alarm 32 = The IPM used in the amplifier detected "High current".
We were told, the replacement Spindle Drive is a good, working unit. So now, we suspect the parameters inside the two Spindle Amplifiers are different and therefore parameter(s) setup is needed for the 'new' drive to work good. Can we access to Spindle drive parameters from the MAPPS MSG-501 Controller? Does anyone have a procedure for re-establishing the parameters into the 'new' drive from the original one above? If & when this is done, we'll give it another go to try & see if the replaced Spindle drive works normal on our machine.
any ideas? thanks again everyone.
sam